 Spiral Staircase Requirements 2026: IBC Dimensions & Egress

Fastest way to avoid rework

Send your location + application + rough dimensions

Share city/region, project type, and rough size. We reply with a project-specific recommendation and quote within one business day.

Updated for 2026 IBC §1011.10 Referenced IRC + NCC Australia Included

IBC Spiral Staircase Requirements 2026: Headroom, Width, Railing & Rise Complete Guide

A complete technical reference for spiral staircase code requirements under IBC 2021 §1011.10, IRC 2021 R311.7.10.1, NCC 2022, and NBC Canada. Covers minimum diameter, clear width, tread geometry, headroom clearance, handrail continuity, egress restrictions, and the most common code violations that cause spiral staircase permit rejections. Written from the perspective of a spiral staircase manufacturer who has shipped compliant systems to 60+ countries.

Code Disclaimer: All requirements reference IBC 2021, IRC 2021, NCC 2022, and NBC 2020 as published. Spiral staircases are subject to the most restrictive jurisdiction-specific interpretations of any stair type. Confirm all dimensions and egress classification with the Authority Having Jurisdiction (AHJ) before permit submission.

Spiral staircases are governed by a dedicated code section (IBC §1011.10) separate from standard staircase provisions — because their geometry creates unique safety challenges that standard stair rules cannot adequately address. This guide explains every dimension, restriction, and condition that applies to spiral staircases in 2026.

What Defines a Spiral Staircase Under IBC?

IBC 2021 defines a spiral staircase with functional precision. Not every circular or helical stair qualifies as a “spiral” under code — and the classification determines which set of rules applies.

IBC 2021 §1011.10 Definition: “A spiral stairway is a form of a stairway in a plan view is a series of winders radiating from a common center and with a column at the center which the treads are attached to or supported by.”

This definition has two required elements: (1) winder treads radiating from a common center, and (2) a central column to which treads are attached or which provides structural support. A circular staircase with a large central void and straight treads is governed differently (as a winder staircase under §1011.8), not as a spiral.

Spiral vs Curved vs Circular: Code Classification

TypeCode ClassificationGoverning SectionKey Characteristic
SpiralIBC §1011.10 / IRC R311.7.10.1Specific spiral provisions applyCentral column; winder treads; continuous rotation
Circular/CurvedIBC §1011.9 (curved stairways)Standard stairway dimensions + radius minimumNo central column; open void at center; treads may be uniform
WinderIBC §1011.8 (winder stairways)Winder tread provisionsDirection-change treads; not continuous rotation

Why the distinction matters: A spiral staircase governed by §1011.10 has a minimum 60-inch diameter, 26-inch clear width, and severe egress restrictions. A curved staircase governed by §1011.9 can be used as primary egress and has a much larger permitted footprint. Misclassifying the stair type produces a code reference error that may not surface until the permit submission.

IBC 2021 §1011.10 — All Dimensional Requirements

IBC §1011.10 is a dedicated section with seven specific dimensional requirements for spiral staircases. Each is non-negotiable when the staircase is used in an IBC-governed occupancy.

ParameterIBC 2021 §1011.10 RequirementNotes / Rationale
Minimum clear width26 inches (660 mm)Measured between the handrail and the outer edge of treads. Not the full diameter.
Minimum overall diameter60 inches (1,524 mm)Outer diameter of the stair structure. Central column + 2× clear width + handrail rail = typically requires 60″+ total.
Maximum riser height9½ inches (241 mm)More generous than standard stair (7″ max) — reflects the different ergonomics of spiral geometry.
Minimum tread depth7½ inches (190 mm) at 12 inches from narrow edgeThe “12 inches from narrow edge” is the walking line for spiral treads — not the centerline of the full tread width.
Minimum headroom78 inches (1,981 mm)Measured vertically in a 26-inch-wide path of travel. Higher than minimum for standard stairs (80″ IBC; 6’8″ IRC).
Tread nosingUniform rise required; consistent tread geometryEach tread must be identical — no variation in rise height or tread depth between steps.
Egress useRestricted — see §1011.10 exceptionNot permitted as a required means of egress for most occupancies. See Section 5 for full restrictions.

IBC vs IRC Side-by-Side Summary

ParameterIBC 2021 §1011.10IRC 2021 R311.7.10.1
Minimum diameter60 inches (1,524 mm)60 inches (1,524 mm)
Minimum clear width26 inches (660 mm)26 inches (660 mm)
Maximum riser height9½ inches (241 mm)9½ inches (241 mm)
Minimum tread depth7½ inches at walk line (12″ from narrow edge)7½ inches at walk line (12″ from narrow edge)
Minimum headroom78 inches (1,981 mm)78 inches (1,981 mm)
Maximum occupant loadRestricted per egress provisionsSingle dwelling unit / individual suite only

IBC and IRC agree: Unlike many code differences between commercial and residential, IBC and IRC specify identical dimensional minimums for spiral staircases. The key difference is in egress classification: IRC restricts spiral stairs to a single dwelling unit; IBC restricts them to certain occupancy exceptions. Both codes reflect the same underlying safety logic.

IRC 2021 R311.7.10.1 — Residential Spiral Staircase Code

The International Residential Code’s spiral staircase provision mirrors IBC’s dimensional requirements but adds a critical scope restriction: spiral stairs may only serve a “single dwelling unit” or an area accessible from a single occupancy.

IRC R311.7.10.1 — Key Requirements

IRC 2021 R311.7.10.1: “Spiral stairways are permitted to be used as a required means of egress from a space not more than 250 square feet (23.2 m²) and serving not more than five occupants, as a second means of egress from a mezzanine or upper level in a single-family dwelling, or as access to any occupiable space in a dwelling unit.”

This is the IRC’s most important spiral staircase provision: the permission to use a spiral staircase as a required means of egress only applies in limited circumstances — serving a space of 250 square feet or less, or serving a mezzanine in a single-family dwelling. A spiral staircase in a multi-story home connecting bedrooms cannot serve as the sole egress path under IRC.

For residential spiral staircase systems manufactured with IRC R311.7.10.1 compliance documentation, stairsmanufacturer.com provides factory-fabricated steel spiral staircases with 60-inch minimum diameter, 9½-inch maximum riser, and 7½-inch walk-line tread depth as standard configuration options, with dimensional certification for permit submission.

Egress Restrictions: When Spiral Stairs Cannot Serve as Means of Egress

The most significant code limitation on spiral staircases is the restriction on their use as required means of egress. This restriction prevents spiral stairs from being used as the primary escape route in most building applications — it is not negotiable through design intent or aesthetic preference.

IBC §1011.10 — Egress Use Conditions

Under IBC §1011.10, spiral staircases may be used as a required means of egress only in specific conditions:

ConditionPermitted as Required Egress?Code Basis
One- and two-family dwellings (R-3 occupancy)✓ Yes — limited to connecting a loft to a floor below, or serving a mezzanineIBC §1011.10 exception
Multi-family residential (R-2 occupancy)✗ No — not permitted as required egress stairIBC §1011.10 — must use standard stairway
Commercial (A, B, M, I occupancies)✗ No — not permitted as required means of egressIBC §1011.10 — width and geometry insufficient
Serving area ≤250 sq ft (mezzanine, loft)✓ Yes — per IRC and limited IBC exceptionsIRC R311.7.10.1 / IBC §1011.10 exception
Supplemental / non-required stair✓ Yes — any occupancy; egress is provided separatelyIBC §1011.10 — applies only to “required” means of egress

Practical implication: The majority of residential and commercial spiral staircase installations are supplemental — they are architectural feature stairs, not the required egress path. When a building has a compliant standard stair serving as the required egress, an additional spiral staircase may be installed without IBC egress restrictions applying to it. The spiral stair must still meet §1011.10 dimensional requirements, but the occupancy and area restrictions on egress use do not constrain a supplemental stair.

Headroom Requirements: How to Calculate for Spiral Geometry

The 78-inch (1,981 mm) headroom requirement applies within the 26-inch clear width of the travel path. Because spiral stairs rotate continuously, the headroom requirement applies at every point along the helical path — not just at the top and bottom. This creates a geometry challenge: the floor opening at the top must be large enough to provide 78 inches of clear height throughout the rotation.

How Spiral Headroom Works

On a standard straight staircase, headroom is checked at the point of minimum clearance (typically where the upper floor structure passes over the stair). On a spiral, the stair rotates under the floor opening — meaning the floor opening must be sized so that at no point in the rotation does the floor structure come within 78 inches of the tread in use.

Floor-to-Floor HeightTypical Risers RequiredTotal Rotation (360° per 12 risers typical)Headroom Check Points
9 ft (2,743 mm)~12 risers at 9″ each~360° totalEvery 30° of rotation
10 ft (3,048 mm)~13–14 risers~390–420°Every 30° of rotation
12 ft (3,658 mm)~15–16 risers~450–480°Every 30° of rotation

Calculating Minimum Floor Opening

For a 60-inch diameter spiral staircase with 78-inch headroom requirement and a standard 9-foot floor-to-floor height (12 risers at 9 inches each = 108 inches total rise), the floor opening must allow 78 inches of clear height at each step in the rotation. The minimum floor opening is typically the same as the stair diameter (60 inches) plus 2–4 inches clearance, but the rotational geometry may require the opening to be slightly enlarged (62–66 inches diameter opening) to maintain 78 inches throughout the full rotation. Verify with structural calculations from the staircase manufacturer.

Structural note: The floor opening also determines the structural trimmer configuration. For a 60-inch opening in a standard wood-framed floor, doubled or tripled trimmer joists are typically required around the opening perimeter. In concrete construction, the core opening must be coordinated with rebar layout before pour. Obtain opening size from the stair manufacturer before structural drawings are finalized.

Handrail & Guard Requirements for Spiral Staircases

Spiral staircases present unique challenges for handrail and guard design because the handrail must follow a continuous helical path, and the guard must be present on the outer (open) side of every tread throughout the entire rotation.

Handrail Requirements

RequirementSpecificationCode Reference
Height34–38 inches (864–965 mm) above nosingIBC §1012.2
ContinuityMust be continuous throughout full rotation — no breaksIBC §1012.4 — spiral handrail is the most demanding continuity case
GraspabilityType I (1¼”–2″ circular) or Type II (4″–6¼” perimeter)IBC §1012.3
Central column handrailNot accepted as a code-compliant handrail — column is not graspable per Type I/II criteriaIBC §1012.3 — profile must meet dimensional requirements
Outer edge handrailRequired on the outer (open) sideIBC §1012.1 — handrail required on stairway open sides
Return at endsRequired — return to column, post, or safety terminalIBC §1012.5

Guard Requirements on Spiral Staircases

The outer edge of a spiral staircase — where the open side of the stair projects beyond the floor opening — requires a guard when the drop exceeds 30 inches (IBC §1015.2). For standard spiral staircases, this means the outer balustrade system must serve as a compliant guard (42 inches for commercial, 36 inches for residential) in addition to supporting the graspable handrail.

LocationGuard Required?Height
Outer edge of spiral (open side)Yes — when drop >30 inches42″ commercial / 36″ residential from nosing
Inner edge (around central column)Not required — solid column provides barrierN/A
Top landing / floor level edgeYes — as per standard floor guard requirements42″ commercial / 36″ residential from floor

For complete spiral staircase railing systems — continuous helical handrail, outer guard balustrade with code-compliant infill, and top landing guard integration — doublebuilding.com designs and fabricates fully integrated spiral stair and railing assemblies, with handrail radius matched to stair diameter and all guard dimensions factory-set to IBC or IRC specifications.

Tread Geometry: the 7.5-Inch Rule and Walking Line

The tread depth requirement for spiral stairs — 7½ inches minimum — is measured at a specific point, not across the full width of the tread. Understanding this measurement correctly is essential to specify a code-compliant spiral staircase.

The Walking Line Concept

Because spiral tread widths are wedge-shaped (narrow at the column, wide at the outer edge), people naturally walk along a path approximately 12 inches from the inner edge (narrow end). IBC §1011.10 and IRC R311.7.10.1 require that the tread depth measured at the walking line (12 inches from the narrow edge) must be at least 7½ inches.

Measurement LocationTread Depth RequirementNotes
At narrow end (column face)No minimum specifiedVaries by design; typically 1–3 inches
At 12 inches from narrow edge (walking line)7½ inches (190 mm) minimumThis is the code measurement point
At outer edgeNo specific maximumDetermined by stair diameter and riser count

How Tread Depth Relates to Stair Diameter

For a 60-inch diameter spiral staircase with a 4-inch central column (typical), the usable tread extends from the column face to the outer handrail — approximately 26 inches. The 12-inch walking line falls in the middle of this range. To achieve 7½ inches at the walking line, the number of treads per revolution must be limited to ensure sufficient arc length per tread.

Stair DiameterMax Treads per 360°Resulting Walk-Line Tread DepthIBC Compliant?
60 inches (1,524 mm)12–13 treads7.5–8.2 inches at 12″ from columnYes — borderline; verify with manufacturer
72 inches (1,829 mm)12–15 treads9.0–11.3 inches at 12″ from columnYes — comfortable compliance
48 inches (1,219 mm)12 treads5.0–6.3 inches at 12″ from columnNo — diameter too small for IBC compliance

48-inch diameter spiral stairs: Many catalog spiral staircase systems are sold at 48-inch diameter. These do NOT meet IBC §1011.10’s 60-inch minimum diameter requirement, nor can they achieve the 7½-inch walk-line tread depth. They may be installed as decorative/supplemental stairs in residential occupancies where egress is provided by other means, but they must not be represented as IBC-compliant egress stairs.

Australia NCC 2022 — Spiral Staircase Requirements

NCC 2022 does not have a separate dedicated section for spiral staircases as distinct from IBC. Instead, NCC governs spiral staircases under its general staircase provisions with specific winder-tread rules. Key requirements are similar but not identical to IBC.

ParameterNCC 2022 (Class 1 — residential)NCC 2022 (Class 2–9 — commercial)
Minimum rise115 mm (4.5″)150 mm (5.9″)
Maximum rise190 mm (7.5″) per H4D3190 mm (7.5″) per D2D8
Minimum going (tread depth)240 mm (9.4″) at walk line250 mm (9.8″) at walk line
Walk line (measurement point)270 mm (10.6″) from narrow edge270 mm from narrow edge
Minimum width (clear)1,000 mm (39.4″) residentialDepends on occupant load — typically 1,000 mm min
Headroom2,000 mm (78.7″) — slightly more than IBC2,000 mm
Handrail height865–1,000 mm from nosing865–1,000 mm from nosing

Key NCC vs IBC difference for spiral stairs: NCC uses a 270 mm (10.6″) walking line vs IBC’s 12-inch (305 mm) walking line. NCC also requires a deeper minimum going (240–250 mm vs 190 mm IBC) but permits a lower maximum riser (190 mm vs 241 mm IBC). An IBC-compliant spiral stair will generally need tread-depth verification before claiming NCC compliance — the two codes use different measurement points and different minimum tread depths.

Canada NBC 2020 — Spiral Staircase Requirements

The National Building Code of Canada 2020 addresses spiral stairs under its general stairway provisions in Division B, Part 3. Like NCC, NBC does not create a distinct “spiral staircase” section but governs winder treads with specific dimensional requirements.

ParameterNBC 2020IBC 2021 (comparison)
Min. clear width900 mm (35.4″)660 mm (26″) — IBC allows narrower
Max. riser height200 mm (7.9″) residential241 mm (9.5″) — IBC is more permissive
Min. tread depth (walk line)150 mm (5.9″) at 300 mm from narrow edge190 mm (7.5″) at 305 mm from narrow edge
Min. headroom1,950 mm (76.8″)1,981 mm (78″) — IBC slightly more
Handrail height865–965 mm from nosing864–965 mm — same range

Floor Opening Size: Calculating the Rough Opening

The rough opening in the floor must accommodate the spiral staircase footprint, the guard system at the top landing, and necessary clearance for installation. Under-sizing the floor opening is the most common field problem with spiral staircase installations.

Minimum Opening vs Recommended Opening

Stair DiameterCode Minimum OpeningRecommended OpeningReason for Larger Recommended
60 inches (1,524 mm)60 inches (1,524 mm)62–64 inches (1,575–1,625 mm)Handrail clearance + installation tolerance
72 inches (1,829 mm)72 inches74–76 inches (1,880–1,930 mm)Handrail clearance + installation tolerance
Custom diameter (D)DD + 2–4 inchesStandard allowance for handrail bracket projection

Structural Coordination Checklist

  • Obtain exact floor opening size from staircase manufacturer before structural drawings are finalized
  • Trimmer joist or beam sizing around the opening requires structural engineer review in wood-frame and steel-frame floors
  • In concrete slabs: opening must be formed before pour; cutting after pour is expensive and may require core reinforcement
  • Top landing guard posts must anchor to floor structure, not to the opening edge framing alone
  • Allow for floor finish thickness — finished floor raises anchor point for column base plate

Materials & Structural Specifications

Spiral staircases are manufactured in several material systems, each with different structural behaviors, maintenance requirements, and compliance documentation needs.

Steel (Carbon / Mild Steel)

The most common structural material for spiral staircases in both residential and commercial applications. Central column: typically 4–6 inch diameter schedule 40 or 80 steel pipe. Treads: 1/4″ or 3/8″ plate with bar grating, perforated plate, or checkered plate finish. Available with powder coat (interior) or hot-dip galvanized (exterior) finish. Structural load verification per AISC 360-22. Carbon steel spiral stairs are the most cost-effective option for standard diameter ranges.

Stainless Steel (304 / 316)

Preferred for coastal, exterior, or architectural feature applications. Grade 316L for saltwater environments — 316’s higher molybdenum content provides superior corrosion resistance per ASTM A276. Stainless steel spiral systems cost 40–80% more than mild steel but eliminate lifetime repainting. Fabrication tolerances are tighter; verify final finish (brushed, mirror, or satin) with the manufacturer before order.

Aluminum

Lightweight, corrosion-resistant, and available in anodized or powder-coated finishes. Limited to lighter residential loads due to aluminum’s lower yield strength compared to steel. Not typically specified for commercial occupancies where IBC §1607.8’s 200-lb concentrated load requirement must be verified. Best application: residential interior supplement staircase, access to loft or mezzanine.

Wood (Decorative)

Wood treads on steel stringers is the most common hybrid for residential feature spiral stairs. Wood species selection affects tread load capacity and surface friction — hardwoods (oak, maple, walnut) are preferred. Wood tread spiral stairs are nearly always supplemental stairs in residential settings. Stain-and-seal or oil finish on wood treads requires re-application per manufacturer schedule to maintain slip resistance per ANSI B101.3.

10 Spiral Staircase Code Violations That Fail Permit

1. Diameter under 60 inches

48-inch catalog spiral stairs do not meet IBC §1011.10 or IRC R311.7.10.1 minimums. Prevention: Specify minimum 60-inch diameter on all drawings; verify with manufacturer before order.

2. Using a spiral as the sole required means of egress

Most occupancies cannot use a spiral staircase as their required egress path. Prevention: Confirm egress classification at programming stage; provide a compliant standard staircase as the required egress path and position the spiral as supplemental.

3. Tread depth measured at the wrong point

Measuring tread depth at the outer edge or at center instead of at 12 inches from the narrow edge produces incorrect (overstated) depth values. Prevention: Require manufacturer to certify walk-line tread depth at 12 inches from narrow edge in compliance documentation.

4. Riser height non-uniform across the flight

Manufacturing tolerances or installation errors can produce variable riser heights. IBC requires uniformity. Prevention: Specify maximum ±3/16 inch riser height variation; verify on-site with level and tape before installation acceptance.

5. Non-continuous handrail (breaks at landing post)

Handrail interrupted at top landing post creates a discontinuity that fails IBC §1012.4. Prevention: Specify continuous helical handrail with smooth transition from stair flight to landing guard; detail connection at top landing in fabrication drawings.

6. Central column used as handrail

The center column of a spiral stair does not meet Type I or Type II handrail profile requirements. It cannot substitute for a code-compliant handrail. Prevention: Specify a separate helical handrail on the outer side of the stair, sized to meet IBC §1012.3 graspability.

7. Headroom measured at bottom of stair only

For spiral stairs, headroom must be verified throughout the entire rotation path — not just at the entry point. Prevention: Require manufacturer’s headroom verification drawing showing clearance at every 30° of rotation.

8. Floor opening too small — stair cannot be installed with guard

A floor opening exactly equal to stair diameter leaves no room for guard posts, handrail brackets, or installation clearance. Prevention: Add 2–4 inches to stair diameter when sizing floor opening; coordinate with structural engineer before structural drawings.

9. Guard height below 42 inches on commercial project

Designer specifies 36-inch guard on a commercial occupancy (IBC) based on residential precedent. Prevention: Confirm occupancy group at project start; commercial spiral stairs require 42-inch guard and 34–38-inch graspable handrail.

10. Misclassifying a curved stair as a spiral stair

A curved staircase with a large open void at center is governed by IBC §1011.9, not §1011.10, and can serve as primary egress with different dimensional requirements. Misclassifying it as a spiral triggers unnecessary restrictions. Prevention: Confirm classification with AHJ at pre-permit conference; provide plan drawings showing central column presence (spiral) or absence (curved).

FAQ — IBC Spiral Staircase Requirements

What is the minimum diameter for an IBC spiral staircase?

IBC 2021 §1011.10 requires a minimum 60-inch (1,524 mm) overall diameter for spiral staircases. IRC 2021 R311.7.10.1 sets the same minimum. This dimension refers to the outer diameter of the stair structure including treads, not the floor opening size. 48-inch diameter spiral stairs do not meet IBC or IRC requirements.

Can a spiral staircase be a primary means of egress under IBC?

Generally, no. IBC §1011.10 restricts spiral staircases from serving as required means of egress in most occupancies. Exceptions apply in one- and two-family dwellings (R-3 occupancy) when the spiral serves a loft or mezzanine, and in spaces of 250 square feet or less. For all other occupancies, a standard stairway must serve as the required egress, and the spiral may be installed as a supplemental (non-required) stair.

What is the maximum riser height for a spiral staircase under IBC?

IBC §1011.10 sets the maximum riser height for spiral staircases at 9½ inches (241 mm) — significantly more generous than the 7-inch maximum for standard stairs. This higher maximum riser is permitted because spiral stair users are expected to exercise greater caution and the typical installation is in lower-traffic residential or supplemental applications.

How is tread depth measured on a spiral staircase?

Tread depth on spiral stairs is measured at the walking line: 12 inches (305 mm) from the narrow edge of the tread. IBC §1011.10 requires a minimum 7½ inches (190 mm) at this point. This measurement is taken along the arc of the tread at the 12-inch walking line radius — not across the chord or at the outer edge.

Does a spiral staircase need a handrail AND a guard?

Yes. A spiral staircase requires both a guard and a handrail. The guard (at 42 inches commercial / 36 inches residential) prevents falls off the open outer edge. The handrail (at 34–38 inches, graspable profile) assists stair users with balance. The central column does NOT satisfy the handrail requirement — a code-compliant helical graspable rail must be provided on the outer side of the stair.

What is the minimum headroom for a spiral staircase?

IBC §1011.10 and IRC R311.7.10.1 both require a minimum headroom of 78 inches (1,981 mm) measured vertically throughout the 26-inch clear width of the stair travel path. This applies at every point in the stair’s rotation — the floor opening must be sized to provide 78 inches of clearance throughout the full helical path, not just at the entry and landing.

Get a Code-Compliant Spiral Staircase Quote

To receive a spiral staircase specification and quote, provide: project location (determines applicable code), floor-to-floor height, required diameter or available floor space, occupancy type (residential/commercial), preferred material (steel/stainless/aluminum), tread material preference, finish, and whether the stair will be supplemental or required egress. We will respond within one business day with a specification confirming IBC or IRC compliance, recommended diameter, riser count, and indicative pricing.

Sources & Code References

  • International Building Code (IBC) 2021. International Code Council. §1011.10 (Spiral Stairways), §1011.9 (Curved Stairways), §1012 (Handrails), §1015 (Guards).
  • International Residential Code (IRC) 2021. International Code Council. R311.7.10.1 (Spiral Stairways), R311.7.8 (Handrails), R312 (Guards).
  • National Construction Code (NCC) 2022. Australian Building Codes Board (ABCB). Volume Two H4D3 (Stairs — Residential), Volume One D2D8 (Stairways — Commercial). Effective 1 May 2023.
  • National Building Code of Canada 2020 (NBC 2020). National Research Council Canada. Division B, Part 3, §3.4.6 (Stair Dimensions and Configuration).
  • ADA Standards for Accessible Design, 2010. U.S. Department of Justice. §504 (Stairways), §505 (Handrails). Note: spiral stairs generally cannot serve accessible routes.
  • AISC 360-22. Specification for Structural Steel Buildings. American Institute of Steel Construction. (Structural requirements for steel spiral staircase column and tread connections.)
  • ASTM A53/A53M-22. Standard Specification for Pipe, Steel, Black and Hot-Dipped Zinc-Coated (Galvanized), Welded and Seamless. (Column pipe specification for steel spiral stairs.)
  • ASTM A276/A276M-17. Standard Specification for Stainless Steel Bars and Shapes. (Stainless steel component specification.)
  • ANSI B101.3-2012. Test Method for Measuring Wet SCOF of Common Hard-Surface Floor Materials. (Slip resistance for spiral stair tread surfaces.)
  • ICC A117.1-2017. Accessible and Usable Buildings and Facilities. (Spiral stairs cannot be used on accessible routes — confirms ADA restriction.)